SERVO VOLTAGE STABILIZERS
Recurring Energy Conservation
- Apart from voltage stabilization, ENERGX servo voltage stabilizers offer several energy conservation possibilities such as:
- By optimizing voltage supply to lighting equipments up to 20% energy saving can be achieved along with increased life of bulbs, tubes and accessories.
- For industrial consumption, similar savings is possible by optimizing the voltage supply to motors. The excessive heating and consumption of motors due to unbalanced voltage can be corrected leading to energy saving and long motor life.
Energx Servo Voltage Stabilizers
Input power is applied across the motor driven variable transformer Which has a center tap that divides that variable transformer into bucking and boosting voltages areas.
The buck-boost transformer is a fixed ratio isolation transformer capable of high amperes at low voltage. The ratio of the transformer is determined by the amount of voltage needed to buck or boost the input line to maintain the specified output level. The buck boost transformer secondary is wired in series with the load and the primary is connected across the variable transformers “Center tap & brush terminals. Depending on which side of the “center tap” (the variable transformer brush is positioned, the variable/buck-boost transformer system will add to (boost) or subtract from (buck) the Input line voltage. The further the variable transformer brush is from the “center tap” the more bucking or boosting of voltage will occur.
The key to the proven reliability and long trouble free service life of a Energx Voltage Stabilizer is in the combination of a motor driven variable transformer With buck boost transformer technology.
Advantages
- Quick, steady and accurate correction of voltage
- Constant output voltage, despite load current variations
- Balanced output voltage, irrespective of input unbalance
- Overall energy saving 98% efficiency increased life of your equipment, reduced heating and minimal losses
- 24 / 7 Customer Support
Typical Applications
- BROADCAST: Regulations for Radio and TV station transmitters, receivers, and mobile production vehicles
- COMMERCIAL: High rise building whole floor regulation or power conditioning, input voltage regulation for elevator control and large A/C chillers
- INDUSTRIAL: Process center power quality improvement, standard or customized test stands for product quality testing or design verification
- MEDICAL: X-Ray, cat scan, and MRI Power conditioning
- MARINE: Dockside or shipboard voltage regulation and bower conditioning.
- CNC: Milling Machine, CNC lathes, EDM’ & Printing Machines
Specifications
SPECIFICATIONS |
THREE PHASE |
SIGLE PHASE |
Capacity | 3KVAto 1000 KVA | 1 KVAvto 50 KVA |
Narrow | 360 v to 460 v | 20 v to 270 v |
Input voltage range | ||
Normal | 340 v to 460 v | 195 v to 270 v |
Wide | 295 v to 465 v | 170 v to 270 v |
Extended | 240 v to 465 v | 140 v to 270 v |
Output Voltage | 380 v/400 v/415 v | 220 v / 230 v / 240 v |
System | Unbalanced | Unbalanced |
Regulation | +/-1% | |
Efficiency | >98% | >98% |
Input Frequency | 50 Hz +/-3Hz | 50 Hz+/-3Hz |
Wave Form | Same as Input | Same as Input |
Control Circuit | Microcontroller based with front panel Calibration | Microcontroller based with front panel Calibration |
Motor drive | Heavy Duty AC Synchronous | Heavy Duty AC Synchronous |
Motor | Motor | |
Correction Rate | 70 v/sec | 35 v/sec |
Over Load PH | Mains On Output On | Mains On Output On |
I/P Low/High | I/P Low/High | |
O/P Low/High | O/P Low/High | |
Metering | Digital display to read | Digital display to read |
Input & Output Voltage | Input & Output Voltage | |
Output Current & Frequency | Output Current & Frequency | |
Operating Temperature | 45 Degrees | 45 Degrees |
Duty Cycle | Continuous | Continuous |
Nature of Cooling | Air Cooled /Oil Cooled | Air Cooled /Oil Cooled |
Protections | Under Voltage & Over Voltage | Under Voltage & Over Voltage |
Over load / short circuit & Phase Sequence | Over load / short circuit & Phase Sequence | |
Stabilizer Standard | As per IS 9815 | As per IS 9815 |
Oil Standard | As per IS 335 | As per IS 335 |
PRODUCTS |
||
Variacs | 2 Amps to 1000 Amps | |
Isolation Transformers | 1 KVA to 250 KVA Air cooled & Oil cooled | |
Step-down Transformers | 0.5 KVA to 250 KVA Air cooled & Oil cooled | |
UPS | 1 KVA to 50 KVA Online & Offline UPS |